GP 31 series 10-40k

True online double conversion with DSP control
Robust electrical performance to prevent damage from top and bottom connections
Screwless cabinet design and fully coating PCBAs to withstand harsh environment
Unique ventilation design for effective heat dissipation
Accepts dual-mains inputs
Front access makes maintenance and replacement easily
High short-circuit and overload capabilities
Easy integration into existing electrical networks or generator
Parallel capability up to 4 units

 Product Function

 

Battery management function

The GP31 series has advanced battery management functions, including the UPS system.Set the battery number and maximum charging current value two parameters.

 

Function of timer switch.

GP31 series UPS system has the function of timing and shutdown, and the cycle cycle of setting parameters is available from single to daily, so that the UPS power supply is more humanized and used by the majority of users.

Output voltage, frequency adjustable function.

The output voltage and frequency of GP31 series UPS system can be set. The output voltage can be set with up to 5 parameters. The output frequency can be set to 50Hz or 60Hz, which can meet the needs of the majority of users.

        

Alarm and protection function.

With various types of alarm through sound, light, LCD, input and output nodes and network transmission mode of the current alarm timely, accurate and detailed, in improving the reliability of the system at the same time, help to maintenance personnel accurately positioning and troubleshooting.

 

Cold start function

UPS does not have ac power input but the battery pack has been in parallel with the dc bus, which can directly start UPS. 

 

The city power restored self-priming function.

Since the launch of mains restore function has a backup battery for UPS equipment applications, can be implemented in backup battery undervoltage protection, input ac back to normal, start UPS power source, according to good work mode choice power supply design in advance.This function and network monitoring to realize unattended UPS automatic startup.

 

Input phase sequence adaptive function.

UPS system with phase sequence adaptive function, when the main road, the bypass input cable installation, even changing the phase sequence of the cable, the system can automatically detect and track locking input phase sequence, the system normal work, making it easier for users to use.

 

Technical Parameters

 

Model

GP3110K

GP3115K

GP3120K

GP3130K

GP3140K

CAPACITY

10KVA /8KW

15KVA /12KW

20KVA /16KW

30KVA /24KW

40KVA /32KW

INPUT

Nominal Voltage

3 x 380VAC (3Ph + G or 3Ph   + N + G )

Acceptable Voltage Range

304VAC ~ 456VAC

Frequency

50 Hz  ± 5Hz (±10%)

OUTPUT

Nominal Voltage

220VAC/230VAC/240VAC   (Selectable)

Connection Type

Hardwire 3-wire (1 Ph+N+G)

Waveform

Pure Sinewave

Output Voltage Stability

Steady state

± 1%

Transient state

± 5%

Frequency

50 Hz

Frequency Stability

± 1%

Frequency Synchronization Range

± 5Hz(Equaltobypassworkingrange)

Frequency Synchronization Speed

1~2 Hz/s

Power Factor

0.8

Crest Factor

3:01

Total Harmonic Distortion (THDv)

<2% (Linear Load)

<4% (Non-linear Load)

Dynamic in-rush Voltage Range

0%->100%->0% (R load)   <±5%:20%->100%->20%(RLoad)±3%

Dynamic Recovery Time (III Grade)

0%~100% RCD load: <60 ms   recover to 90% of nominal voltage

Phase Displacement

120 ° ± 1% (balanced load)

120°±2%(imbalances50%oftheload)

Transfer Time

0 ms

Overload Capability

0%~110% continuous running;   110%~ 150% for 10 min~1 min; >160% for 200 ms

Short-circuit Capability

60~100ms

Transient Response Time

< 5ms

BYPASS

Connection Type

Hardwire 3-wire (1Ph+N+G)

Input Voltage Range

220VAC ±25%

Overload Capability

1.5 In~1.8 In 1h~30s

Short-circuit Capability

1.8 In~ >2.0 In   30s~200ms

SYSTEM

Efficiency (At Linear Load and 270VDC)

85%

86%

86%

88%

90%

ECO Mode (Non-parallel models)

Yes

EPO Function

Yes

Standard

IEC 61000-4-5 Protection   surge, IEC 62040-2 EMC/EMI, IEC62040-1 Safety

BATTERY

Battery

Type

Support VRLA Battery

Numbers

16-18 pcs

Reverse Diode

Yes

Cold Start

Yes

PHYSICAL

IP Protection

IP20 (Default), IP21/IP31   (Optional)

Dimension, D x W x H (mm)

570x450x900

700x450x1050

Net Weight (kgs)

125

135

200

280

310

ENVIRONMENT

Operating Temperature

0~35°C continuous running,   40°C 8-hour running at nominal input voltage, recharging batteries and no   overload, 45°C derating to 85% with linear load

Humidity

0~90% (non-condensing)

Noise Level

Less than 70dB @ 1 Meter

MANAGEMENT

Modbus RS-232/RS485

Supports Windows   2000/2003/XP/Vista/2008/7/8, Linux, and MAC

Dry Contacts

6 outputs and 2 inputs

Optional SNMP

Power managemetn from SNMP   manager and web browser