GPI 31 series 10-120kva

Product featuresGPI series is a harsh environment for the standardization of the whole industrial UPS, can easily work together with your facilities monitoring system, to provide all the industrial design alternatives, the standard of high level of protection (IP) 31, aimed at 9th level seismic design, and from 10 to + 45 ° C wide temperature range.It also has top and bottom cable entrances, and fully integrated isolation transformer options.The GPI series is one of the most easily deployed, installed and maintained UPS in the same category with full frontal maintenance operations and back wall mounting.

Product features:


GPI series is a harsh environment for the standardization of the whole industrial UPS, can easily work together with your facilities monitoring system, to provide all the industrial design alternatives, the standard of high level of protection (IP) 31, aimed at 9th level seismic design, and from 10 to + 45 ° C wide temperature range.It also has top and bottom cable entrances, and fully integrated isolation transformer options.The GPI series is one of the most easily deployed, installed and maintained UPS in the same category with full frontal maintenance operations and back wall mounting.

 

Full digital control technology.

All GPI series UPS power converter (such as rectifier, inverter, etc.) and system components (such as bypass and static inverter switch) is controlled by the advanced DSP (digital signal processor).The high speed and precise control performance of DSP has greatly improved the accuracy of UPS control and enhanced the reliability.

 

Superior power grid adaptability.

The GPI series U P S has a range of ultra wide input voltage (304~456VAC), and the input frequency range (50Hz + + 10%), which is suitable for the application conditions of severe electrical network.Wide UPS input power range, maximum possible to prevent the battery unnecessary discharge, prolong battery life and availability.

 

Advanced parallel function.

The parallel function increases the capacity of the UPS system and improves the reliability of the power supply.For example, in the N+1 system, assuming that 1 UPS is out due to accidental failure, the remaining system can still improve the stable power supply to the precision load.

 

Reliability

Life expectancy is greater than 20 years, and can work normally at 40 degrees Celsius.It can be connected to two independent municipal power supply system.Three - in single UPS can be connected to a battery pack or a 220 v dc screen.Both fan failure and redundant cooling system can ensure the system is fully loaded.

 

The physical environment

All the circuit boards are sprayed with anti-corrosion insulating paint, which has insulation, moisture-proof, anti-leakage, shockproof, dustproof, anti-corrosion, anti-aging and electrical resistance.The design of natural convection, independent air duct and thermal shunt are introduced in the ventilation mode.Adapt to high temperature, high humidity, dust, salt alkali, corrosive gas, vibration and other bad working conditions.

 

Intelligent man-machine conversation

GPI series standard with 4.7-inch screen, optional 10 inch color graphic touch screen.


Technical parameter list:


Model

3110K-6P

3115K-6P

3120K-6P

3130K-6P

3140K-12P

3160K-12P

3180K-12P

31100K-12P

31120K-12P

Capacity

10KVA/8KW

15KVA/12KW

20KVA/16KW

30KVA/24KW

40KVA/32KW

60KVA/48KW

80KVA/64KW

100KVA/80KW

120KVA/96KW

INPUT

 Nominal voltage

3 x 380VAC/400VAC (3Ph + N)

VOLTAGE RANGE

304VAC ~ 456VAC

Frequency range

50/60 Hz ± 10 %

OUTPUT

Output voltage

220VAC/230VAC/240VAC (optional)

Voltage   stability

Steady state: typical value/transient: + 5% typical   value (load variation 100-0-100%)

Transient: + 5% typical value (load variation   100-0-100%)

frequency lock-in range

50/60 Hz synchronous plus or minus 1 % city power loss   + 0.1hz.

Frequency tracking rate

±1 Hz/s

Output waveform

Sine wave

Total harmonic (THD)

<2% (linear load) <5% (nonlinear load)

 Overload capacity

110% ~ 150% 10min~1min; 150% ~ >160% 1min~200ms;   200ms for >160%

Crest factor

3:1

Efficiency

90%

91%

93%

Rectifier

Type

6 pulse

12 pulse

Bypass


Type

Static switch

Voltage range

220V±25%

System

ECO mode

Supports the whole machine efficiency 98% in ECO/ECO   mode.

Over temperature protection

Inverter/charger/rectifier (90 ° C)

Maintenance bypass

Standard manual maintenance bypass.

Battery & charge

The battery section number

18PCS

Charging Current

20A

Communication interface

Standard communication interface.

Standard communication interface. EPO, parallel   interface, dry contact interface, USB, RS232, RS485, intelligent slot.

Structure parameter

Size (mm)

800*800*1800

1200*800*1800

1600*800*1800

Net Weight  (Kgs)

370

390

460

650

680

1000

1260

1360

1620